RKI Instruments, M2 Series, Stand Alone Explosion Proof Transmitter

RKI Instruments, M2 Series, Stand Alone Explosion Proof Transmitter
Click to enlarge
Price: $900.00
Model: Gas MM2 Series, Stand Alone Explosion Proof Transmitter
Manufacturer: RKI Instruments
Specifications Click Here for Specs
Average Rating: Not Rated
Available Options:
Select an M2 Series, Stand Alone Explosion Proof Transmitter for Purchase:

From RKI Instruments,

The RKI M2™, a state-of-the-art transmitter that can operate as an independent, stand-alone system or as part of an integrated system. The M2 connects with an analog or digital signal to virtually any controller, PLC, or DCS. Setup procedures are simplified with user friendly push buttons and LCD menus. It utilizes a magnetic wand technique for performing non-intrusive calibration. The M2 provides an automatic zero drift correction feature, which results in more stable readings and reduces the need for adjustments due to sensor aging.

The housing of the M2 does not need to be opened for zeroing or calibration, making it unnecessary to declassify the area for routine maintenance. It is designed so that a complete field calibration can be performed by one person. Sensor construction is rated Class I, Div. 1 groups B, C, D for flammables, CO, H2S, O2, and CO2, and Class I, Div. 2 for all other toxics.

The transmitter provides a 4-20 mA output in addition to a Modbus digital output. It also has two levels of alarms with relays, plus a fail alarm with relay. A digital display of the gas concentration, as well as alarm and status lights, can be viewed through the front window.

The toxic sensors are electrochemical type plug-in sensors, which provide high specificity, fast response, and long life. The plug-in design allows quick replacement in the field with no tools required. Toxic sensors are designed for use in Class I, Div. 2 hazardous locations. Sensors available for Cl2, NH3, SO2, PH3, ASH3, and HCN.

The M2 represents the latest leading edge technology in sensor / transmitters today.

Features Include:

  • Operates with or without a controller
  • Direct digital readout on backlit LCD
  • Available gases include
  • %LEL, H2S, CO, PPM HC, and CO2
  • Toxic gases include Cl2, NH3, SO2, HCN, and more
  • Infrared sensor for combustibles and CO2
  • 4-20 mA & digital Modbus outputs standard
  • 2 fully programmable alarm relays & fail relay
  • Non-intrusive calibration via magnetic wand
  • Explosion proof construction
  • Patented water repellent sensor cover
  • User friendly setup, push buttons & LCD menus
  • Long-life sensors (2 + years typical)

Applications Include:

  • Petrochemical plants
  • Refineries
  • Offshore drilling platforms
  • Water & wastewater treatment plants
  • Offshore oil rigs
  • Pulp & paper mills
  • Gas, telephone, & electric utilities
  • Parking garages
  • Manufacturing facilities
  • Steel
  • Automotive

Available Explosion Proof Assemblies-

Part Number                Description

65-2610RK                    LEL 0-100% sensor (catalytic) / transmitter with j-box, UL version

65-2610RK-05               LEL 0-100% sensor (catalytic) / transmitter with j-box, CSA version

65-2611RK                    Hydrogen (H2) specific 0-100% LEL sensor / transmitter with j-box, UL version

65-2611RK-05               Hydrogen (H2) specific 0-100% LEL sensor / transmitter with j-box, CSA version

65-2619RK-CH4            IR Methane (CH4) 0-100% LEL, sensor / transmitter, with j-box, UL version

65-2619RK-HC              IR Hydrocarbons (isobutane) 0-100% LEL, sensor / transmitter with j-box, UL version

65-2628RK-CH4            IR Methane (CH4) 0-100% volume, sensor / transmitter, with j-box

65-2613RK-05               Oxygen (O2) 0 - 25% sensor (capillary type) / transmitter with j-box, explosion proof, CSA version

65-2616RK-05               Carbon Monoxide (CO) 0-300 ppm sensor / transmitter with j-box, CSA version

65-2615RK-05               Hydrogen Sulfide (H2S) 0-100 ppm sensor / transmitter with j-box, CSA version

65-2630RK-02               IR Carbon Dioxide 0-5,000 ppm, sensor / transmitter with j-box, UL version

65-2630RK-03               IR Carbon Dioxide 0-5%, sensor / transmitter with j-box, UL version

65-2630RK-05               IR Carbon Dioxide 0-50%, sensor / transmitter with j-box, UL version

65-2630RK-10               IR Carbon Dioxide 0-100%, sensor / transmitter with j-box, UL version


Available Non-Explosion Proof Assemblies-

Part Number                Description

65-2613RK                    Oxygen (O2) 0 - 25% sensor (capillary type) / transmitter with j-box (non explosion proof)

65-2614RK                    Oxygen (O2) 0-25% sensor / transmitter with j-box (partial pressure sensor) (non explosion proof)

65-2632RK                    Hydrogen Sulfide (H2S) 0-100 ppm sensor / transmitter, non explosion proof with j-box

65-2633RK                    Carbon Monoxide (CO) 0-300 ppm sensor / transmitter, non explosion proof with j-box

65-2631RK-02               IR Carbon Dioxide (CO2) 0-5,000 ppm, sensor / transmitter, non explosion proof with j-box

65-2631RK-03               IR Carbon Dioxide (CO2) 0-5%, sensor / transmitter, non explosion proof with j-box

65-2631RK-05               IR Carbon Dioxide (CO2) 0-50%, sensor / transmitter, non explosion proof with j-box

65-2631RK-10               M2, IR Carbon Dioxide (CO2) 0-100%, sensor / transmitter, non explosion proof with j-box